下面是艾默生公司技术人员现场演示的翻译文档.
today we are going to demonstrate the power of our predictive intelligence from our plant web
今天我们将使用Rosemont 30501S压力变送器
technology using the Rosemont 30501s pressure transmit
展示设备的智能预测功能
the 3051 s is a highly accurate device that's used to measure pressure DP level and DP flow
3051S是用来测量差压液位和流量的高精度仪表
now using the advanced diagnostics available with the 3051s
现在我们使用3051s来演示一下
we can also detect problems in the process such as a plug impulse line
我们可以检测取压管道堵塞等问题
as you may know impulse lines can plug do the dirty process or freezing of the line
当工艺介质粘稠或脏污的时候,取压管会堵住
when this happens the transmitter is unable to respond to process changes
当取压管堵住后压力变送器无法及时采集管道中的数据
and this will result in misleading pressure measurements
压力变送器会显示一个错误的数据
unfortunately the user does not know when a line has become plugged
而且我们并不知道取压管发生了堵塞
this is because the pressure in the line gets trapped
因为压力没有传感过来
and the transmitter will continue to provide the same measurement as before the plug
压力变送器会一直显示同一个值
this misleading measurement will not be discovered for some time
有时候并不会发现这些错误
and by then the plug impulse line may have affected the quality of your process and your product
会导致生产受到影响
to illustrate this plug line issue one will slowly close this valve
为了模拟取压管的堵塞
on impulse line leading to the 3051s
我们缓慢关闭压力变送器
if an impulse line becomes plugged technicians should be aware of this
当取压管堵塞了会有诊断技术检测到
The plant web alert can be displayed on the workstations
在操作站上会有报警
that technicians are using to monitor the field devices
这项技术用于监测现场智能设备
as you can tell the plant web alert is flashing on the alarm banner
操作员站画面报警一栏上面
notifying us of the abnormal situation
会有闪烁提醒我们
click on the alarm banner to open up the faceplate to investigate further
点击报警一栏
you can click on the AMS device manager icon
然后点击AMS的按钮
as you can see in addition to just measuring pressure
除了能够显示压力值后
the 3051 s is also measuring the amount of processed variability
还可以显示压力数值的变化趋势
in this case here the process variability decreased which allowed us to trigger an alert
在上述情况下,压力下降曲线异常
that told us it deviated too much from the baseline
AMS智能设备管理系统会提示系统发生报警
in traditional practice without these advanced Diagnostics
如果没有这些的诊断措施
we would not have known about the plugged impulse line
我们不会知道取压管堵塞了
by being able to detect the plug line we can take proactive measures to resolve the issue
DCS上检测到这个故障后
before affects the quality of the process
可以及时处理,防止产生事故
下一篇:罗斯蒙特压力变送器全新阀组产品!
版权与免责声明:凡本网注明“来源:亚洲制造网”的所有作品,均为浙江兴旺宝明通网络有限公司-亚洲制造网合法拥有版权或有权使用的作品,未经本网授权不得转载、摘编或利用其它方式使用上述作品。已经本网授权使用作品的,应在授权范围内使用,并注明“来源:亚洲制造网”。违反上述声明者,本网将追究其相关法律责任。 本网转载并注明自其它来源(非亚洲制造网)的作品,目的在于传递更多信息,并不代表本网赞同其观点或和对其真实性负责,不承担此类作品侵权行为的直接责任及连带责任。其他媒体、网站或个人从本网转载时,必须保留本网注明的作品第一来源,并自负版权等法律责任。 如涉及作品内容、版权等问题,请在作品发表之日起一周内与本网联系,否则视为放弃相关权利。